  RIMSAFE Metallic tube type UL Listed / Vds Approved Linear Heat Detection
Appreciation
Approval
Picture of typical installation layout
“Rimsafe” Floating Roof Tank Rim Seal System is a fully automated system aimed at detecting of the fire occurring within the rim seal area owing to reasons like lightening strike, static electricity, etc and to detect such a fire at the incipient stage automatically and to deploy the extinguishing agent instantly on the entire periphery of the rim seal area and thus to extinguish the fire rapidly.
The Rim Seal System consist of a highly intelligent microprocessor based Linear Heat Detector connected with a hollow metallic tube (SS/Copper), which acts as the heat sensor. The intelligent linear heat detection evaluation unit works on the principal of detection of rate of rise in temperature and maximum pressure. When the user set pre-configured parameters exceeds, the system determines occurrence of a fire, triggers audiovisual alarm and actuates the extinguishing system.
The Extinguishing system consists of foam vessels / modules of suitable capacity designed as per NFPA/OISD 117/118 standards to meet the extinguishing requirements and to cover the rim seal area. Pre-mixed Aqueous Film Forming Foam solution is used as the Extinguishing Agent. N2 gas is used as an expellant for discharging of the foam out of the vessels. The Linear Heat Detection system actuates the foam based extinguishing system.
 
 
RIMSAFE SYSTEM – FAIL SAFE FEATURES
 
RIMSAFE SYSTEM – PROVEN TRACKRECORD
 
 
 